Ships have a weird electrical system. Someone here might recognize what I'm describing. We don't have a hot, neutral, and ground. If you place a meter in the outlet between the two blades, you get 120 volts. If you place a meter between one blade and the ground prong, you'll get roughly 75 volts, and if you put the meter between the other blade and ground, you get about 65 volts. So, both blades are hot, but, you'd think the two blades would be 60 volts each (kinda like the two legs of a 240 outlet... each one is 120 volts). Instead, the two legs here are 65 and 75 which would add up to 140 volts... however you get 120.

A few years back, I asked the chief engineer about it, then the first engineer and second... not one of them could explain it to me!! All they know is it works as 120 when you put them together. And to think... these engineers have been there nearly 20 years!

So, if any of you electrical whizzes recognize what I described, please explain it.
__________________
Charlie Trahan


He who dies with the most toys still dies.
Reply With Quote
  #2  
Old 10-28-2009, 10:03 PM
jeyurkon's Avatar
jeyurkon jeyurkon is offline
VideoKarma Member
 
Join Date: Oct 2008
Location: Central Michigan
Posts: 1,699
Quote:
Originally Posted by Charlie View Post
Ships have a weird electrical system. Someone here might recognize what I'm describing. We don't have a hot, neutral, and ground. If you place a meter in the outlet between the two blades, you get 120 volts. If you place a meter between one blade and the ground prong, you'll get roughly 75 volts, and if you put the meter between the other blade and ground, you get about 65 volts. So, both blades are hot, but, you'd think the two blades would be 60 volts each (kinda like the two legs of a 240 outlet... each one is 120 volts). Instead, the two legs here are 65 and 75 which would add up to 140 volts... however you get 120.

A few years back, I asked the chief engineer about it, then the first engineer and second... not one of them could explain it to me!! All they know is it works as 120 when you put them together. And to think... these engineers have been there nearly 20 years!

So, if any of you electrical whizzes recognize what I described, please explain it.
Sounds like they're 120 degree apart as in a 3-phase system, instead of 180 degrees in 2-phase. That would explan it additing up to 120. Maybe it was supposed to be 70 volts on each leg and was shifted due to the particular loading of the system.

John
Reply With Quote
  #3  
Old 10-28-2009, 11:55 PM
wa2ise's Avatar
wa2ise wa2ise is offline
VideoKarma Member
 
Join Date: Dec 2002
Location: USA
Posts: 3,147
Exclamation

Quote:
Originally Posted by jeyurkon View Post
Sounds like they're 120 degree apart as in a 3-phase system, instead of 180 degrees in 2-phase. That would explain it adding up to 120. Maybe it was supposed to be 70 volts on each leg and was shifted due to the particular loading of the system.

John
It might be a delta system, 120V on each side of the equilateral triangle. And they probably have a set of three lightbulbs going from each line to the ship's hull. That would yield the 65 to 75V you measured (the mismatch being manufacturing variation of the light bulbs), and all three bulbs would glow dimly. If one line shorts to the hull, the electrical system continues to function, and 2 of the three light bulbs will light up brightly, telling the chief engineer that the short exists, and which phase has the short (the one with the dark light bulb).
__________________
Reply With Quote
  #4  
Old 10-29-2009, 12:09 AM
Charlie's Avatar
Charlie Charlie is offline
On Land
 
Join Date: Aug 2002
Location: Warren, TX
Posts: 2,582
Quote:
Originally Posted by wa2ise View Post
If one line shorts to the hull, the electrical system continues to function, and 2 of the three light bulbs will light up brightly, telling the chief engineer that the short exists, and which phase has the short (the one with the dark light bulb).
I think you might have won the prize. There's a panel in the emergency gen room that has three small lights, and from time to time, one is lit differently from the other two, and the engineers start looking for shorts. In most cases, this happens following heavy rain or seas and it's nothing more than water in an outside light fixture somewhere. There has been an occasion or two in which it was more serious.
__________________
Charlie Trahan


He who dies with the most toys still dies.
Reply With Quote
Reply


Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off

Forum Jump


All times are GMT -5. The time now is 02:46 AM.



Powered by vBulletin® Version 3.8.4
Copyright ©2000 - 2026, Jelsoft Enterprises Ltd.
©Copyright 2012 VideoKarma.org, All rights reserved.