Actually, lower line frequency is hard on the power transformer. To a first order approximation, a power transformer designed for 120V 25Hz can be used on 240V 50Hz no problem, though all its secondaries will produce twice the voltage. And the opposite direction: a 120V 60Hz transformer can only take 50V at 25Hz. And a combo transformer designed for 240V/120V 50/60Hz can take 144V in 120V mode at 60Hz, if it could take 240V at 50Hz. In general, the higher the line freq, the smaller the core can be for the same power rating. Airplanes used 400Hz AC as that allowed the use of smaller and lighter transformers.

So fetch up some 400Hz... for some easy going electricity.